Fan-Coil-Unit-Performance-Parameter |
|||||||||||
Model performance |
RNFP-34 |
RNFP-51 |
RNFP-68 |
RNFP-85 |
RNFP-102 |
RNFP-136 |
RNFP-170 |
RNFP-204 |
RNFP-238 |
||
Rated air volume (m³h) |
H |
340 |
510 |
680 |
850 |
1020 |
1360 |
1700 |
2040 |
2380 |
|
H |
260 |
390 |
510 |
640 |
770 |
1020 |
1280 |
1530 |
1790 |
||
H |
170 |
260 |
340 |
430 |
510 |
680 |
850 |
1020 |
1190 |
||
Rated cooling capacity |
KW |
H |
1.8 |
2.7 |
3.6 |
4.5 |
5.4 |
7.2 |
9.0 |
10.8 |
12.6 |
Kcal/h |
H |
1548 |
2322 |
3096 |
3870 |
4644 |
6192 |
7740 |
9288 |
10836 |
|
Rated heat |
KW |
H |
2.7 |
4.05 |
5.4 |
6.75 |
8.1 |
10.8 |
13.5 |
16.2 |
18.9 |
Kcal/h |
H |
2322 |
3483 |
4644 |
5805 |
6966 |
9288 |
11610 |
13932 |
16254 |
|
Input power (W) |
12pa |
H |
36 |
50 |
60 |
74 |
93 |
130 |
147 |
183 |
221 |
30pa |
H |
43 |
57 |
70 |
84 |
105 |
151 |
169 |
206 |
245 |
|
50pa |
H |
48 |
64 |
0.81 |
97 |
114 |
169 |
204 |
243 |
291 |
|
Noise dB(A) |
12pa |
H |
37 |
39 |
41 |
43 |
45 |
46 |
48 |
50 |
52 |
30pa |
H |
40 |
42 |
44 |
46 |
47 |
48 |
50 |
52 |
54 |
|
50pa |
H |
42 |
44 |
46 |
47 |
49 |
50 |
52 |
54 |
56 |
|
Water quantity(kg/h) |
319 |
478 |
638 |
797 |
956 |
1275 |
1594 |
1913 |
2232 |
||
Hydraulic loss(kPa) |
≤30 |
≤30 |
≤30 |
≤30 |
≤40 |
≤40 |
≤40 |
≤40 |
≤50 |
||
Gross weight (About)kg |
WA |
12 |
15 |
16 |
18 |
19 |
25 |
29 |
33 |
36 |
|
Bring back the bellows. |
14 |
17 |
19 |
21 |
23 |
30 |
34 |
38 |
42 |
||
WM |
24 |
28 |
30 |
33 |
36 |
47 |
58 |
61 |
64 |
||
LM |
27 |
32 |
33.5 |
36.5 |
39.5 |
50.5 |
62 |
65 |
68 |
||
KM |
22 |
31 |
35 |
37.5 |
|||||||
Inlet- und Outlet-Wasserrohre |
3/4 ′ Internal thread |
||||||||||
Condensate pipe (except KM) |
3/4′ External thread |
||||||||||
Power supply |
AC220/50 HZ |
||||||||||
Note |
1. Cooling operating parameters: inlet air dry bulb temperature 27°C, wet bulb temperature 19,5 °C, inlet water temperature 7°C, water temperature difference 5°C. 2. Heating operating parameters: inlet air dry bulb temperature 21°C, inlet water temperature 60°C, hot water flow rate same as cooling operating conditions. 3. The unit has undergone a pressure test at 2,0 MPa and is allowed to operate at a maximum working pressure of 1.6MPa. 4. There are also four-Pipe (one plus two, two plus two, three plus one) units available. |
||||||||||